Description
Schneider Contactor Product Features Series: TeSys TeSys Deca Product name: TeSys D TeSys Deca Product or component type: Auxiliary contact block Product group: LADN Series compatibility: TeSys D CAD TeSys D LC1D TeSys F LC1F TeSys F CR1F TeSys Deca CAD TeSys Deca LC1D Mounting position: Front Pole contact arrangement: 2 NO + 2 NC Contacts operation: Instantaneous [Ue] nominal operating voltage: 690 V AC 25…400 Hz [Ie] nominal operating current: 6 A at 120 V AC -15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13 [Ui] nominal insulation voltage : 690 V conforming to IEC 60947-5 -1 Conforming to 600 VUL 60947-5-1 Conforming to 600 VCSA C22.2 No 60947-5-1 [Ith] classical open air thermal current: 10 A at